If this option is enabled, the NX-6 will send an “Exit Error Report” when an entry/exit zone
is faulted, at the instant the exit delay expires. This report will be sent together with the
user number that was used to arm the system, provided that the panel is not disarmed
before the entry delay expires. The alarm report will also be sent. Even if this feature is
not enabled, the siren will sound if any entry/exit zone is faulted, as soon as the exit delay
expires (see location 23 segment 3).
Expander trouble
The NX-6 will report expander trouble to the central station if this option is enabled. This
condition will light up the “Service” LED on the keypad, even if it is not reported.
NOTE: The keypads are considered to be expanders. The number of expansion devices
that are reported can be found in appendix 3 (see location 37 segment 3).
Early to Open/ Late to Close
If an opening occurs before the opening and closing times, the NX-6 will send an “Early
Open” report. If it fails to close on or before the designated closing time, the NX-6 will
send a “Late to Close”report. (see location 23 segment 4)
Fail to communicate
The NX-6 will light up the “Service” LED if a report fails to reach the central station. If this
option is enabled, a fail to communicate code will be reported when the next report is
successfully communicated. A fail to communicate is always logged as “data lost”
(see location 37 segment 4).
Final set door
If this feature is enabled, it will only be applicable for secondary entry/exit zones (f.e.
configuration group 9 or 19). If the final set door option is enabled, the exit time will
immediately expire as soon as the secondary entry/exit zone (type 9 or 19) becomes
ready again. This feature can only be used in combination with magnetic contracts (see
location 23, segment 2, option 8).
Fire alarm verification
When this feature is enabled, the NX-6 will verify a fire alarm by requiring more than one
trip on a smoke detector (the same or another one) within a specified time (120-255
seconds) before it generates an alarm (see location 40 segment 9).
First opening/last closing report for multiple partitions
If this feature is enabled, the NX-6 will only transmit a closing report after ALL partitions
have been armed. An opening report will be sent as soon as one partition has been
disarmed (see location 37).
Force arming
If this option is enabled, the NX-6 can be “Force Armed” when zones have been violated.
In this condition, the “Ready” LED will flash if a “Force Armable” zone is not secure. At the
end of the exit delay, these zones will become bypassed. If these zones become secured
at any time during the arming cycle, they will be unbypassed and will become active in
the system. If “Bypass Report” is enabled, the force arming zones can be programmed to
report bypass when they are force armed (default), or not to report bypass even if
“Bypass Report” is enabled (see locations 37 segment 5, and 111-169 segment 2).