Programming zone configuration groups
LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE CONFIGURATIONS AS
LISTED IN THE TABLE ON PAGES 44-46. THESE LOCATIONS ARE CONSIDERED
AS ADVANCED PROGRAMMING, AND THEY SHOULD ONLY BE CHANGED IF YOU
HAVE A THOROUGH UNDERSTANDING OF THE OPERATION OF EACH BIT.
LOCATION 110 - CONFIGURATION GROUP 1 ALARM EVENT CODE (1 segment, numerical data)
Location 110 contains the event code that is sent for a Contact ID or SIA report. The
desired event code should be chosen from the list on pages 121-122. The zone ID will be
the zone that is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may
also contain the alarm report code for the Robofon format (value 00-99).
LOCATION 111 - CONFIGURATION GROUP 1 CHARACTERISTIC SELECT (5 segments, feature
selection data)
Segment 1
1 = Fire (turn on if this is a fire zone)
2 = 24 hour (turn on for non-fire 24 hour zones)
3 = Keyswitch zone (normally open switch)
4 =
Follower (turn on for burglary zones that are Instant during non-
entry times)
5 = Delay 1 zone (follows timer 1 Entry and Exit times)
6 = Delay 2 zone (follows timer 2 Entry and Exit times)
7 =
Interior (turn on if this zone should Automatically Bypass or
Bypass for Stay Arming)
8 = Local only (turn on if this zone should not be reported)
Remark: for a maintained keyswitch (ON/OFF), program both
“keyswitch” and “local”
Segment 2
1 = On: if configuration group will beep the keypad for alarm
2 = On: if configuration group will sound the yelping siren for alarm
3 = On: if configuration group will sound the steady siren for alarm
4 = On: if configuration group will chime
5 = On: if configuration group can be bypassed
6 = On: if configuration group is included in the group shunt
7 = On: if configuration group is force armable
8 = On: if configuration group is entry guard
Segment 3
1 = On: enables Fast Loop Response. (50mS) - Off= 500mS
2 =
On: enables Double End Of Line Tamper zone. (Mainly used for
tamper on wireless zones)
3 = On: enables Trouble Reporting zone. (Day zone and Fire zones)
4 = On: if configuration group is a Cross Zone
5 = On: enables Dialler Delay zone. (See location 40)
6 =
On: if configuration group will use swinger shutdown. (See
location 38)
7 = On: enables Restore reporting
8 = On: enables Listen-In. (See location 40)